Purpose
GAES/GADS are designed for extract from small garages and car parks where the rules require two independent fans. The unit fits straight into the duct, and the outlet backdraft dampers stop air from flowing back through a stopped fan.
Design
Two direct-driven backward-curved fans sit in a casing of aluminium profiles and galvanised panels with mineral wool. The external-rotor motors have thermal contacts and separate terminal boxes; each fan’s speed can be controlled over the full range.
When to choose
- a small car park with ductwork;
- redundant extract is needed without a separate plant room;
- for higher airflow, choose the GAB / GAPF cabinets or the two-stage AXG.
Technical data
| Sizes | 175, 225, 250, 31/310, 355, 400 |
|---|---|
| Motor | External rotor with thermal contacts, a separate terminal box per motor; 100 % speed control (electronic or transformer controller) |
| Materials | Aluminium profile frame with glass-fibre polyamide corners; galvanised panels lined with mineral wool; steel or plastic impellers balanced to G2.5 |
| Mounting | In-line in a rectangular duct |
| Power supply | GAES — 230 V / 50 Hz, GADS — 400 V / 50 Hz |
| Airflow | approx. up to 8,000 m³/h (upper end of the selection charts) |
| Pressure | approx. up to 1,200 Pa |
Versions
- GAES — single-phase 230 V motors
- GADS — three-phase 400 V motors
- Ex stb — explosion-proof, speed-controllable version
Accessories
- Backdraft dampers (standard)
- Flexible duct connections
Manufacturer documentation is available on request — name the series in the enquiry form.