HimpelMade in Korea

Himpel HueVen Eco ERV with a washable core

A 2026 ducted ceiling ERV with a polymer membrane core that can be washed. The controller measures CO₂, particulate matter and volatile organic compounds and switches the unit to automatic mode by CO₂ level.

Airflow
150–250 m³/h
Sizes
HRD-200EPI; HRD-200EPI_U (with UV module)

Features

  • Washable core. The polymer membrane of the enthalpy core can be washed; the manufacturer cites thermal-shock and ageing tests of the membrane from −25 to +70 °C.
  • Air-quality automation. A controller with CO₂, PM and TVOC sensors switches the unit to automatic mode by CO₂ level.
  • Filtration. Pre-filter and H13 HEPA as standard; on request H14, an organic-salt filter or a copper pre-filter.
  • Control. AiroT app; zoned room-by-room control as an option.

Models

ModelAirflow, m³/hPower, WEfficiency, heating / cooling
HRD-200EPI250 / 200 / 15087 / 62 / 3681 / 73 %
HRD-200EPI_U250 / 200 / 15095 / 70 / 3880 / 72 %

Typical uses

Apartments from 66 m², serviced apartments and houses with ducted ventilation. Compare with EBN / EBSN if you need up to 270 m³/h or a more compact casing.

Technical data

Airflow150–250 m³/h
SizesHRD-200EPI; HRD-200EPI_U (with UV module)
MotorBLDC; three speeds — 250 / 200 / 150 m³/h
MaterialsEnthalpy core with a washable polymer membrane
MountingAbove a false ceiling; four Ø 125 spigots, Ø 100 branch ducts
Recovery efficiency, heating / cooling81 / 73 % (HRD-200EPI); 80 / 72 % (HRD-200EPI_U)
Power input87 / 62 / 36 W; with UV module 95 / 70 / 38 W
Noise levelno more than 50 dB
Filterspre-filter + H13 HEPA; on request H14 HEPA, organic-salt HEPA, copper pre-filter
Modesventilation, automatic (CO₂), bypass, air purification
Coreper the manufacturer, the membrane is tested for thermal shock and ageing from −25 to +70 °C
Dimensions and weight620 × 680 × 320 mm, 15 kg

Versions

  • HRD-200EPI — base model
  • HRD-200EPI_U — with a photocatalytic UV module
  • Zoned (room-by-room) control as an option

Data are from the Himpel catalogue (March 2026) for a 220 V / 60 Hz supply. We confirm the 50 Hz version and its performance for each model at selection.

Request a selection

Himpel HueVen Eco selection

Tell us about the project — an engineer will reply within one business day.

You can send drawings in reply to our first e-mail.