HimpelMade in Korea

Himpel HueVen EGI commercial ERVs

Ducted ERVs in a galvanised steel casing for offices, commercial premises, schools and clinics. Six models from 170 to 1,100 m³/h with 70–100 Pa external static pressure.

Airflow
170–1,100 m³/h
Pressure
70–100 Pa

Models

ModelAirflow, m³/hPower, WExternal pressure, PaEfficiency, heating / coolingWeight
HRE-S150170657071 / 61 %23 kg
HRE-S250(D)270997070 / 52 %25 kg
HRE-350(D)37015010070 / 56 %32 kg
HRE-500(D)55019510075 / 65 %38 kg
HRE-800(D)85035210077 / 66 %65 kg
HRE-1000(D)1,10046410072 / 60 %65 kg

Airflow and power are at top speed.

Typical uses

Offices, shops and commercial premises, schools and kindergartens, clinics, and commercial units in residential complexes. An external static pressure of 70–100 Pa allows a duct network with grilles to be connected.

Comparison

If air purification with air-quality sensors is needed alongside ventilation, consider the floor-standing HueVen S.

Technical data

Airflow170–1,100 m³/h
Pressure70–100 Pa
MaterialsGalvanised steel (EGI) casing
MountingAbove a false ceiling; Ø 125/150 ducts (up to HRE-350), Ø 200/250 (HRE-500…1000)
Noise levelno more than 50 dB
Filterspre-filter + medium filter
Controlcentral control and wired controller as options
Weight23–65 kg
Names on the manufacturer’s English websiteHRE1-150EGI … HRE1-1000EGI
Power supply1~ 220 V / 60 Hz per the catalogue

Data are from the Himpel catalogue (March 2026) for a 220 V / 60 Hz supply. We confirm the 50 Hz version and its performance for each model at selection. In Korea this line is sold to construction companies only — we confirm export availability on request.